Phoenix MINI MCR-2-UI-UI-PT-isolation amplifier 2902040,3-terminal isolation amplifier, using plug-in connection technology, with calibration measurement range switching function, can be used for electrical isolation of unipolar and bipolar analog signals. The input/output can be configured via a DIP switch. Plug-in connection technology, standard configuration.

Use Restrictions
EMC Description EMC: Class A products, see the manufacturer's declaration in the download area

Product Type isolation amplifier
Product Series MINI Analog Pro
Channels 1
Model isolation amplifier
configuration DIP switch
insulation characteristics: GB Standard
Overvoltage Category II
pollution level 2

electrical isolation 3 End Isolation
galvanic isolation between input and output is
cut-off frequency (3dB) 30Hz (via DIP switch)
5 kHz (via DIP switch)
protection circuit transient protection
step response (10-90%) < 12 ms (with 30Hz filter)
maximum temperature coefficient 0.01 %/K
temperature coefficient, typical 0.01 %/K
Maximum transmission error ≤ 0.1 % (maximum configured output range)
≤ 0.15 % (final value, IN:4 mA ... 20 mA / OUT:-10V ... 10V)
Electrical isolation input/output/power supply
Rated insulation voltage 300Vrms
Test Voltage 3 kV AC (50 Hz, 60 s)
insulation reinforced insulation conforming to IEC/EN 61010-1
Power
Rated supply voltage 24V DC
Supply Voltage Range 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Typical current consumption 25 mA (24V DC current output with load)
54 mA (current output, 12V DC including load)
power consumption ≤ 800 mW (IOUT= 20 mA,9.6V DC,600 Ω load)

signal: current/voltage
Input Number 1
configurable/programmable is
voltage input signal 0V ... 5V (via DIP switch)
1V ... 5V (via DIP switch)
-5V ... 5V (via DIP switch)
0V ... 10V (via DIP switch)
2V ... 10V (via DIP switch)
-10V ... 10V (via DIP switch)
0V ... 20V (via DIP switch)
4V ... 20V (via DIP switch)
-20V ... 20V (via DIP switch)
0V ... 24V (via DIP switch)
4.8V ... 24V (via DIP switch)
-24V ... 24V (via DIP switch)
0V ... 30V (via DIP switch)
6V ... 30V (via DIP switch)
-30V ... 30V (via DIP switch)
Maximum voltage input signal 33V
current input signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
-20 mA ... 20 mA (via DIP switch)
Maximum current input signal 24 mA
input voltage > 1000 kΩ
input current approx. 63 Ω (+0.7V for testing diodes)

signal: current/voltage
outputs 1
configurable/programmable is
voltage output signal 0V ... 5V (via DIP switch)
1V ... 5V (via DIP switch)
-5V ... 5V (via DIP switch)
0V ... 10V (via DIP switch)
2V ... 10V (via DIP switch)
-10V ... 10V (via DIP switch)
No-load voltage < 17V
current output signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
Maximum current output signal 22 mA
short-circuit current < 32 mA
load/output load voltage output ≥ 10 kΩ
load/output load current output ≤ 600 Ω (when 20 mA)
fluctuation < 20 mVSS(at 600 Ω)
< 20 mVSS(at 600 Ω)
2902040

Phoenix MINI MCR-2-UI-UI-PT-Isolation Amplifier 2902040