EMC: Class A products, see the manufacturer's declaration in the download area
Product Type
Feeder Isolator
Product Series
MINI Analog
Channels
1
insulation characteristics
Overvoltage Category
II
pollution level
2
electrical isolation
3 End Isolation
galvanic isolation between input and output
is
cut-off frequency (3dB)
approx. 100Hz
rated conditions
508 mW (24V DC)
208 mW (24V DC)
protection circuit
transient protection
Signal Transmission Behavior
In = Out
step response (10-90%)
3.5 ms
maximum temperature coefficient
< 0.01 %/K
temperature coefficient, typical
< 0.002 %/K
Maximum transmission error
≤ 0.2 % (of terminal value)
Typical transmission error
≤ 0.1 % (of terminal value)
Electrical isolation input/output/power supply
Rated insulation voltage
50V AC/DC
Test Voltage
1.5 kV AC (50 Hz, 60 s)
insulation
foundation isolation conforming to IEC/EN 61010
Power
Rated supply voltage
24V DC
Supply Voltage Range
19.2V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
power consumption
< 900 mW (24VDC, feeder isolator operation)
< 600 mW (24VDC, isolator operation)
signals: current
Input Description
sensor circuit
Input Number
1
current input signal
0 mA ... 20 mA (Isolator operation)
4 mA ... 20 mA (feeder isolator and isolator operation)
Maximum current input signal
28 mA
input current
approx. 50 Ω
Transmitter supply voltage
UBmaximum 4.5V, applicable load 0mA... 20mA
Transmitter supply voltage range
14.7V DC ... 25.5V DC
signals: current
outputs
1
No-load voltage
about 12.5V
current output signal
0 mA ... 20 mA (Isolator operation)
4 mA ... 20 mA (feeder isolator and isolator operation)