Phoenix MINI MCR-2-UNI-UI-UIRO-PT-isolation amplifier 2902028, a 4-terminal isolation amplifier that can be universally configured, adopts switching output and plug-in connection technology for electrical isolation of analog signals. Configuration via DIP switch or software. Plug-in connection technology, standard configuration.

Use Restrictions
EMC Description EMC: Class A products, see the manufacturer's declaration in the download area

Product Type isolation amplifier
product series MINI Analog Pro
Channels 1
Model isolation amplifier
configuration DIP switch
Software
Application
insulation characteristics: GB Standard
Overvoltage Category II
pollution level 2

electrical isolation 4 road isolation
galvanic isolation between input and output is
step response (0-99%) 140 ms (15Hz sample rate)
45 ms (60Hz sample rate)
25 ms (240Hz sampling rate, software only)
maximum temperature coefficient 0.01 %/K
temperature coefficient, typical 0.01 %/K
Maximum transmission error 0.1 % (of terminal value)
Electrical isolation input/output/power supply
Rated insulation voltage 300Vrms
Test Voltage 3 kV AC (50 Hz, 60 s)
insulation reinforced insulation conforming to IEC/EN 61010-1
power supply
Rated supply voltage 24V DC
Supply Voltage Range 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Typical current consumption 32 mA (24V DC)
63 mA (12V DC)
power consumption ≤ 1W (IOUT= 20 mA,9.6V DC,600 Ω load)

signal: current/voltage
Input Number 1
configurable/programmable is
voltage input signal 0V ... 10V (via DIP switch)
2V ... 10V (via DIP switch)
0V ... 5V (via DIP switch)
1V ... 5V (via DIP switch)
10V ... 0V (via DIP switch)
10V ... 2V (via DIP switch)
5V ... 0V (via DIP switch)
5V ... 1V (via DIP switch)
0V ... 12V (can be set via software)
Maximum voltage input signal 12V
current input signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
20 mA ... 0 mA (via DIP switch)
20 mA ... 4 mA (via DIP switch)
10 mA ... 0 mA (via DIP switch)
10 mA ... 2 mA (via DIP switch)
0 mA ... 24 mA (can be set via software)
Maximum current input signal 24 mA
input voltage > 120 kΩ
input current approx. 50 Ω (+0.7V for testing diodes)

switching: transistor
outputs 1
Contact Type 1 N/O contact
Minimum Switching Voltage 1V
maximum switching voltage 30V DC
minimum switching current 100 µA
maximum switching current 100 mA (at 30V)
signal: current/voltage
outputs 1
configurable/programmable is
voltage output signal 0V ... 10V (via DIP switch)
2V ... 10V (via DIP switch)
0V ... 5V (via DIP switch)
1V ... 5V (via DIP switch)
0V ... 10.5V (can be set via software)
Maximum voltage output signal about 12.3V
current output signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Maximum current output signal 24.6 mA
load/output load voltage output ≥ 10 kΩ
load/output load current output ≤ 600 Ω (when 20 mA)
fluctuation < 20 mVSS(at 600 Ω)
< 20 mVSS(at 600 Ω)
2902040

Phoenix MINI MCR-2-UNI-UI-UIRO-PT-Isolation Amplifier 2902028

Product Center

PRODUCT CENTER