Phoenix MINI MCR-BL-I-2I-signal multiplier 2810829,4-terminal signal multiplier, used for electrical isolation and replication of analog signals, screw wiring, input signal: 4 mA ... 20 mA, output signal 2 x 4 mA ... 20 mA
Use Restrictions | |
EMC Description | EMC: Class A products, see the manufacturer's declaration in the download area |
Product Type | Signal Multiplier |
Product Series | MINI Analog |
Channels | 2 |
Model | Input Isolation Amplifier |
configuration | INTERBUS |
insulation characteristics | |
Overvoltage Category | II |
pollution level | 2 |
Function | |
configuration | INTERBUS |
electrical isolation | 4 road isolation |
cut-off frequency (3dB) | about 35Hz |
protection circuit | transient protection |
step response (10-90%) | 500 ms |
maximum temperature coefficient | < 0.01 %/K |
temperature coefficient, typical | < 0.004 %/K |
Maximum transmission error | ≤ 0.2 % (of terminal value) |
Typical transmission error | < 0.1% |
Electrical isolation input/output/power supply | |
Rated insulation voltage | 50V AC/DC |
Test Voltage | 1.5 kV AC (50 Hz, 60 s) |
insulation | foundation isolation conforming to IEC/EN 61010 |
Power | |
Rated supply voltage | 24V DC ±10% |
Supply Voltage Range | 19.2V DC ... 30V DC |
Maximum current consumption | < 30 mA |
power consumption | < 600 mW |
signals: current | |
Input Number | 1 |
configurable/programmable | No |
current input signal | 4 mA ... 20 mA |
Maximum current input signal | 50 mA |
input current | approx. 50 Ω |
signals: current | |
outputs | 2 |
No-load voltage | 9V |
current output signal | 2x 4 mA ... 20 mA |
Maximum current output signal | 20.5 mA |
load/output load current output | ≤ 250 Ω (at 20 mA) |
fluctuation | < 20 mVSS(at 250 Ω) |
Connection Mode | screw connection |
stripping length | 12mm |
thread | M3 |
Rigid conductor cross section | 0.2 mm² ... 2.5 mm² |
Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
Attachable Guide Cross Section AWG | 26 ... 12 |