Phoenix MACX MCR-EX-SL-RPSSI-I-SP-power/input isolation amplifier 2924016,Ex I feed isolator and input isolation amplifier, HART transparent. 0/4 of the potential explosive zone... The 20 mA feed or active signal is sent to the load (active or passive) in the safe area. 3-way electrically isolated, SIL 2 according to IEC 61508, using in-line connection

Product Type Feeder Isolator
Product Series MACX Analog
Application Analog Input
Channels 1
Model Ex I Isolation Amplifier with SIL Functional Safety

electrical isolation 3 End Isolation
galvanic isolation between input and output is
Signal Transmission Behavior In = Out
step response (10-90%) < 200 & micro;s (for jumpers 4 mA ... 20 mA, load 600 Ω)
< 600 & micro;s (for jumpers 0 mA ... 20 mA, load 600 Ω)
maximum temperature coefficient < 0.01 %/K
temperature coefficient, typical < 0.004 %/K
Maximum transmission error < 0.1 % (final value 20 mA)
Typical transmission error < 0.05 % (final value 20 mA)
prevents polarity reversal is
electrical isolation
Test Voltage 2.5 kV AC (50 Hz, 60 s)
Overvoltage Category II
pollution level 2
Electrically isolated input/output/power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
insulation security isolation
electrical isolation input/output IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated input/power supply IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated output/power IEC/EN 60079-7
Standards/Regulations IEC/EN 60079-7
Rated insulation voltage 265Vrms
power supply
Name Feeder Isolator Operation
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 76 mA (24V DC / 20 mA / 1000 Ω)
< 55 mA (24V DC / 20 mA / 250 Ω)
power consumption < 1.1W (24V DC / 20 mA / 1000 Ω)
< 0.95W (24V DC / 20 mA / 250 Ω)
< 1.2W (24V DC / 20 mA / 0 Ω)
power consumption < 1.8W (20 mA / 1000 Ω)
< 1.3W (20 mA / 250 Ω)
power supply
Name Feeder Isolator Operation
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 44 mA (24V DC / 20 mA / 1000 Ω)
< 27 mA (24V DC / 20 mA / 250 Ω)
power consumption < 0.75W (24V DC / 20 mA / 1000 Ω)
< 0.65W (24V DC / 20 mA / 250 Ω)
< 0.95W (24V DC / 20 mA / 0 Ω)

signal: feeder isolator operation
Input Description Active Current Input, Inwhere-Ampere
Input Number 1
input signal current
current input signal 4 mA ... 20 mA
Current Limit 25 mA
Transmitter supply voltage > 16V (20 mA)
> 15.3V (22.5 mA)
Polarization and Surge Protection is
undervoltage/overvoltage signal range 0 mA ... 24 mA (extended transmission range for diagnostics)
2865340

Phoenix MACX MCR-EX-SL-RPSSI-I-SP-Power/Input Isolation Amplifier 2924016

Product Center