Phoenix MACX MCR-SL-RPSSI-I-SP-power/input isolation amplifier 2924207, feed isolator and input isolation amplifier, HART transparent. The 0/4... A 20 mA feed or active signal is sent to the load (active or passive). 3-way electrical isolation, SIL 2 according to IEC 61508 standard.
Product Type | Feeder Isolator |
product series | MACX Analog |
Application | Analog Input |
Channels | 1 |
Model | Isolation Amplifier with SIL Functional Safety |
electrical isolation | 3 End Isolation |
galvanic isolation between input and output | is |
signal transmission behavior | In = Out |
step response (10-90%) | < 200 & micro;s (for jumpers 4 mA ... 20 mA, load 600 Ω) |
< 600 & micro;s (for jumpers 0 mA ... 20 mA, load 600 Ω) | |
maximum temperature coefficient | < 0.01 %/K |
Maximum transmission error | < 0.1 % (final value 20 mA) |
Typical transmission error | < 0.05 % (final value 20 mA) |
electrical isolation | |
Test Voltage | 2.5 kV AC (50 Hz, 60 s) |
Overvoltage Category | II |
pollution level | 2 |
Electrically isolated input/output/power supply IEC/EN 61010-1 | |
Standards/Regulations | IEC/EN 61010-1 |
Rated insulation voltage | 300Vrms |
insulation | security isolation |
electrical isolation input/output IEC/EN 60079-11 | |
Standards/Regulations | IEC/EN 60079-11 |
Rated insulation voltage | 265Vrms |
galvanically isolated input/power supply IEC/EN 60079-11 | |
Standards/Regulations | IEC/EN 60079-11 |
Rated insulation voltage | 265Vrms |
galvanically isolated output/power supply IEC/EN 60079-7 | |
Standards/Regulations | IEC/EN 60079-7 |
Rated insulation voltage | 265Vrms |
Power | |
Name | Feeder Isolator Operation |
Rated supply voltage | 24V DC -20 % ... +25% |
Supply Voltage Range | 19.2V DC ... 30V DC |
Maximum current consumption | < 76 mA (24V DC / 20 mA / 1000 Ω) |
< 55 mA (24V DC / 20 mA / 250 Ω) | |
power consumption | < 1.1W (24V DC / 20 mA / 1000 Ω) |
< 0.95W (24V DC / 20 mA / 250 Ω) | |
< 1.2W (24V DC / 20 mA / 0 Ω) | |
power consumption | < 1.8W (20 mA / 1000 Ω) |
< 1.3W (20 mA / 250 Ω) | |
Power | |
Name | Feeder Isolator Operation |
Rated supply voltage | 24V DC -20 % ... +25% |
Supply Voltage Range | 19.2V DC ... 30V DC |
Maximum current consumption | < 44 mA (24V DC / 20 mA / 1000 Ω) |
< 27 mA (24V DC / 20 mA / 250 Ω) | |
power consumption | < 0.75W (24V DC / 20 mA / 1000 Ω) |
< 0.65W (24V DC / 20 mA / 250 Ω) | |
< 0.95W (24V DC / 20 mA / 0 Ω) |
signal: feeder isolator operation | |
Input Description | active current input |
Input Number | 1 |
input signal | current |
current input signal | 4 mA ... 20 mA |
Current Limit | 25 mA |
Transmitter supply voltage | > 21.5V (20 mA) |
> 20.8V (24 mA) | |
undervoltage/overvoltage signal range | 0 mA ... 24 mA (extended transmission range for diagnostics) |
signal: feeder isolator operation | |
Input Description | Passive current input |
current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
voltage drop | < 3.5V (input isolation amplifier operation) |
undervoltage/overvoltage signal range | 0 mA ... 24 mA (extended transmission range for diagnostics) |