Phoenix MINI MCR-2-RPS-I-I-OLP-feed isolator 2906446, a 2-way feed isolator powered by a single-channel output loop, using in-line connection technology for galvanic isolation of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. Screw connection technology.
Product Type | Feeder Isolator |
Product Series | MINI Analog Pro |
Channels | 1 |
Model | isolation amplifier |
insulation characteristics: GB Standard | |
Overvoltage Category | II |
pollution level | 2 |
electrical isolation | 2 road isolation |
galvanic isolation between input and output | is |
cut-off frequency (3dB) | 100Hz |
Signal Transmission Behavior | In = Out |
maximum temperature coefficient | ≤ 0.001 %/K |
Maximum transmission error | ≤ 0.1 % (5 V) |
Electrical isolation input/output/power supply | |
Rated insulation voltage | 300Vrms |
Test Voltage | 3 kV AC (50 Hz, 60 s) |
insulation | reinforced insulation conforming to IEC/EN 61010-1 |
power supply | |
Supply Voltage Range | 8V DC ... 30V DC (loop power supply, no external power supply required) |
power consumption | 600 mW (25 mA) |
signals: current | |
Number of inputs | 1 |
configurable/programmable | No |
current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
voltage loss | 3.1V (I = 20 mA) |
Transmitter supply voltage | UA- 5V |
additional error, depending on input voltage | (UA- 5 V) x 0.06% |
signals: current | |
outputs | 1 |
configurable/programmable | No |
current output signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
response current | 200 µA |
voltage loss | 3.1V (I = 20 mA) |
load/output load current output | 600 Ω |
Connection Mode | screw connection |
stripping length | 10mm |
thread | M3 |
Rigid conductor cross section | 0.2 mm² ... 1.5 mm² (with cold press head) |
0.14 mm² ... 2.5 mm² (without cold head) | |
Flexible Wire Cross Section | 0.14 mm² ... 2.5 mm² |
Connectable Guide Cross Section AWG | 24 ... 12 (flexible) |
Tightening torque | 0.5 Nm ... 0.6 Nm |