Phoenix MINI MCR-2-T-REL-PT-Threshold Switch 2905633, a universally configurable temperature limit switch with normally open relay output for connection to 2-, 3-and 4-wire resistance thermometers and thermocouples. Configuration via DIP switch or software. Plug-in connection technology
Product Type
threshold switch
Product Series
MINI Analog Pro
Channels
1
Model
isolation amplifier
configuration
DIP switch
Software
Application
insulation characteristics: GB Standard
Overvoltage Category
II
pollution level
2
Function
configuration
DIP switch
Software
Application
Switching Point Accuracy
< 0.1%
step response (0-99%)
300 ms
570 ms
380 ms
300 ms
570 ms
maximum temperature coefficient
0.01 %/K
Electrical isolation input/output/power supply
Rated insulation voltage
300Vrms
Test Voltage
3 kV AC (50 Hz, 60 s)
insulation
reinforced insulation conforming to IEC/EN 61010-1
Power
Rated supply voltage
24V DC
Supply Voltage Range
9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Typical current consumption
44 mA (12V DC)
22 mA (24V DC)
power consumption (I output)
570 mW
signal
Input Number
1
measurement
Input Number
1
configurable/programmable
is
Available Sensor Types (RTDs)
Platinum, Nickel, Copper Sensors
Available Sensor Types (TC)
B, E, J, K, N, R, S, T, L, U, A- 1, A- 2, A- 3, M, L
valid input source
resistance thermometer
thermocouple
Temperature measurement range
-250°C ... 2500°C (RTD)
Temperature measurement range
≥ 20 K (RTD)
sensor type:
500°C ... 1820°C
-230°C ... 1000°C
-210°C ... 1200°C
-250°C ... 1372°C
-200°C ... 1300°C
-50°C ... 1768°C
-50°C ... 1768°C
-200°C ... 400°C
-200°C ... 900°C
-200°C ... 600°C
0°C ... 2500°C
0°C ... 1800°C
0°C ... 1800°C
-200°C ... 100°C
-200°C ... 800°C
Sensor Input Current
200 µA (RTD)
2902040
넳넲