Phoenix PLC-RPT-230UC/21HC-relay module 2900297,PLC-INTERFACE suitable for high continuous current, including PLC-BPT.../21 HC base terminal, using plug-in connection, with plug-in micro relay, for installation on DIN rail NS 35/7.5, the limit continuous current is up to 10 A,1 PDT, input voltage 230V AC/DC
Product Type
Relay Module
product series
PLC-INTERFACE
Application
Large impact current
Mode of operation
100% operating factor
mechanical life
3x 107Switch Times
insulation characteristics
insulation
safety isolation, reinforced insulation
Overvoltage Category
III
pollution level
3
Data Management Status
Last data maintenance date
20.03.2025
rated conditions
0.99W
Rated overvoltage
6 kV
coil side
Rated input voltage UN
230V AC
220V DC
Input Voltage Range
179.4V AC ... 264.5V AC (20 °C)
171.6V DC ... 264V DC (20 °C)
rated voltage ("hot" plug electromagnetic relay)
110V DC
drives and functions
monostable
drive (polarity)
polarization
UN
4.3 mA (available for 220V DC)
4.5 mA (230V AC)
Typical Response Time
7 ms
Typical release time
10 ms
protection circuit
bridge rectifier
Operating voltage display
yellow LED
switching
Contact Type
1 changeover contact
Switch Contact Type
Single contact
Contact Material
AgNi
maximum switching voltage
250V AC/DC (When the voltage between the same terminals of two adjacent modules is greater than 250V(L1, L2, L3), a spacer PLC-ATP must be used. FBST 8-PLC... or... FBST 500... for equipotential bridging)
Minimum Switching Voltage
12V (10 mA)
limit continuous current
10 A
6 A (This value only applies to terminal 12. If terminal 12 is shorted, the rating of the relay is used.)
Maximum impact current
30 A (300 ms)
minimum switching current
10 mA (12 V)
Maximum power rating (resistive load)
240W (24V DC)
58W (available for 48V DC)
48W (available for 60V DC)
50W (available for 110V DC)
80W (available for 220V DC)
2500 VA (available for 250V AC)
bridge power rating (resistive load)
144W (24V DC This value is only applicable to terminal 12. If terminal 12 is shorted, the rated value of the relay is used.)
1500 VA (250V AC This value is only applicable to terminal 12. If terminal 12 is shorted, the rating of the relay is used.)