Phoenix MCR-SL-CUC-500-I-universal transmitter 2308085, universal current transmitter, used to measure DC, AC and distortion current, 0 ... 500 A input current, 4 ... 20 mA output
Product Type
Current transmitter
insulation characteristics
Overvoltage Category
III
pollution level
2
Electrical characteristics
Linearity Error
<± 1% (from end of range)
rated conditions
1W
step response (10-90%)
150 ms
temperature coefficient, typical
0.02 %/K (0°C ... 60 °C)
0.04 %/K (-40°C ... 65 °C)
Maximum transmission error
<± 1% (of terminal value)
Rated insulation voltage
300V AC
electrically isolated input/output
Test Voltage
3.5 kV AC (50 Hz, 60 s)
Electrically isolated input/power supply
Test Voltage
3.5 kV AC (50 Hz, 60 s)
Overview
Accuracy
1
Power
Rated supply voltage
24V DC
Supply Voltage Range
20V DC ... 30V DC
Maximum current consumption
(30 + IOUT ) mA
power consumption
1.65W
input data
measurement
Input Number
1
Input current range
0 A AC/DC ... 500 A AC/DC
Overload
3.6 x IIN
Frequency measurement range
20Hz ... 6000Hz (0 Hz)
Curve Type
AC, DC, or distorted current
current transformer
Rated frequency: Standard converter
20Hz ... 6000Hz
Rated primary current Isn
500 A
Accuracy
1
output data
signals: current
current output signal
4 mA ... 20 mA
Maximum current output signal
< 25 mA
load/output load current output
< 300 Ω
connection data
Connection Mode
in-line connection
stripping length
10mm
Rigid conductor cross section
0.25 mm² ... 2.5 mm²
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 12
Connection Mode
perforated connection
Dimensions
Product Size
width
90mm
height
33.8mm
depth
85mm
Round wire
diameter
32mm