Phoenix MCR-SL-CUC-500-I-universal transmitter 2308085, universal current transmitter, used to measure DC, AC and distortion current, 0 ... 500 A input current, 4 ... 20 mA output

Product Type Current transmitter
insulation characteristics
Overvoltage Category III
pollution level 2

Linearity Error <± 1% (from end of range)
rated conditions 1W
step response (10-90%) 150 ms
temperature coefficient, typical 0.02 %/K (0°C ... 60 °C)
0.04 %/K (-40°C ... 65 °C)
Maximum transmission error <± 1% (of terminal value)
Rated insulation voltage 300V AC
electrically isolated input/output
Test Voltage 3.5 kV AC (50 Hz, 60 s)
Electrically isolated input/power supply
Test Voltage 3.5 kV AC (50 Hz, 60 s)
Overview
Accuracy 1
Power
Rated supply voltage 24V DC
Supply Voltage Range 20V DC ... 30V DC
Maximum current consumption (30 + IOUT) mA
power consumption 1.65W

measurement
Input Number 1
Input current range 0 A AC/DC ... 500 A AC/DC
Overload 3.6 x IIN
Frequency measurement range 20Hz ... 6000Hz (0 Hz)
Curve Type AC, DC, or distorted current
current transformer
Rated frequency: Standard converter 20Hz ... 6000Hz
Rated primary current Isn 500 A
Accuracy 1

signals: current
current output signal 4 mA ... 20 mA
Maximum current output signal < 25 mA
load/output load current output < 300 Ω

Connection Mode in-line connection
stripping length 10mm
Rigid conductor cross section 0.25 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 12
Connection Mode perforated connection

Product Size
width 90mm
height 33.8mm
depth 85mm
Round wire
diameter 32mm
2308030

Phoenix MCR-SL-CUC-500-I-Universal Transmitter 2308085

Product Center

PRODUCT CENTER