Phoenix MCR-SLP-1-5-UI-0-current transmitter 2814359,MCR passive current measurement transmitter, input sinusoidal AC current 0 .. 1A AC/0 .. 5A AC, no switching value output, output signal 0 .. 10V/0 .. 20mA

Product Type Current transmitter
insulation characteristics
Overvoltage Category III
pollution level 2

total error ≤ 1.175 % (temperature range)
Test Voltage 3.5 kV
Measurement Level III
step response (10-90%) < 200 ms
maximum temperature coefficient < 0.015 %/K
Maximum transmission error < 0.5 % (of terminal value)
Rated insulation voltage 300V AC (ground)

signal
configurable/programmable No
measurement
Input current range 0 A AC ... 1 A AC (Permissible continuous overload: 120%)
Overload 2xIN(60°C ambient temperature for 5 minutes)
surge strength 50A(1s)
allowable output range 1.2xIN
Rated frequency fN 50Hz
Frequency measurement range 45Hz ... 60Hz
power consumption 1.6 VA (IA= 20mA)
Curve Type Sine
measurement
Input current range 0 A AC ... 5 A AC (Permissible continuous overload: 120%)
impact waveform Sine
Overload 2xIN(60°C ambient temperature for 5 minutes)
surge strength 100 A (1 s)
allowable output range 1.2xIN
Rated frequency fN 50Hz
Frequency measurement range 45Hz ... 60Hz
power consumption 2.2 VA (I = 20 mA)

signals: voltage
voltage output signal 0V ... 10V
Maximum voltage output signal 20V
load/output load voltage output > 100 kΩ
fluctuation < 50 mVSS
signals: current
current output signal 0 mA ... 20 mA
Maximum current output signal 30 mA
load/output load current output < 750 Ω
< 250 Ω (when both current and voltage output are used at the same time)
fluctuation < 50 mVSS
Residual wave, reference measured value 0.5 % (measured value expression)

Connection Mode screw connection
stripping length 8mm
thread M3
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 14
2814728