Phoenix FA MCR-HT-1TS-I-OLP-top mounted transmitter 1145210, the front transmitter powered by the output loop can transmit RTD and TC sensor signals as well as signals from resistance sensors and voltage sensors through 4 mA ... 20 mA. HART, standard configuration, screw connection
Product Type
temperature measurement transmitter
Product Series
Field Analog
Channels
1
configuration
Software
HART
insulation characteristics
Overvoltage Category
II
pollution level
2
Function
configuration
Software
HART
step response (0-99%)
1 s (TC)
1 s (RTD)
electrically isolated input/output
Test Voltage
2 kV AC (50 Hz, 60 s)
power supply
Supply Voltage Range
loop power supply, no external power supply required
10V DC ... 36V DC (Standard product)
measurement
Input Number
1
Input Voltage Range
-20 mV ... 100 mV (minimum measuring range: 5 mV)
Available Sensor Types (RTDs)
Pt, Ni, Cu sensors: 2, 3, 4 wires
Available Sensor Types (TC)
A, B, C, D, E, J, K, L, N, R, S, T, U
Temperature measurement range
-250°C ... 2500°C (range depends on sensor type)
Temperature measurement range
≥ 10 K (RTD)
≥ 50 K (TC)
Linear resistance measuring range
10 Ω ... 2000 Ω (minimum measuring range: 10 Ω)
signals: current
current output signal
4 mA ... 20 mA (HART)
20 mA ... 4 mA (HART)
Maximum current output signal
23 mA
load
(UL- 10 V) / 0.023 A
HART coding
FSK ± 0.5 mA
HART protocol version
7
transmission speed
1200 Baud
Power Filter
50/60Hz
communication resistance
≥ 250 Ω
impact suppression
7 s (HART)
7 s (measured value)
Connection Mode
screw connection
stripping length
8mm
thread
M3
Rigid conductor cross section
0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 14
Tightening torque
0.5 Nm
Explosion-proof installation (EPL)
Gc
Div. 2
Data Communication (Bypass)
Supported Protocols
HART
environmental conditions
protection level
IP00 (IP66/67 installed in magnetic enclosure, NEMA 4X)
ambient temperature (operation)
-40°C ... 85°C
ambient temperature (storage/transport)
-50°C ... 100°C
elevation
≤ 4000 m (above sea level)
climate class
C1
Allowable humidity (operating)
5%... 95% (condensable)
1145210
넳넲
Phoenix FA MCR-HT-1TS-I-OLP-top mounted transmitter 1145210