Phoenix ECM-UC-100A-UI-current transmitter 1136513, a current transmitter used to measure alternating current, direct current and distortion current. Configuration via web server via USB-C interface (24V DC is not required). Current measurement range: 0 A ... 125 A. Standard configuration, in-line connection
Product Type
Current transmitter
insulation characteristics
insulation
safety isolation conforming to IEC/EN 61010-1
Overvoltage Category
III (300 V)
pollution level
2
step response (10-90%)
200 ms (AC/DC)
20 ms (DC)
maximum temperature coefficient
< 0.02 %/K
Maximum transmission error
0.5 % (under rated state, within rated range)
Rated insulation voltage
300V AC (ground)
electrical isolation IEC 61010-2-030
Standards/Regulations
IEC 61010-2-030
Measurement Type
III (300 V)
electrically isolated input/output
Test Voltage
4 kV AC (50 Hz, 60 s)
Electrically isolated input/power supply
Test Voltage
4 kV AC (50 Hz, 60 s)
galvanically isolated output/power
Test Voltage
2 kV AC (50 Hz, 60 s)
power supply
Rated supply voltage
24V DC
Rated supply voltage range
12V DC ... 24V DC -20 % ... +25%
Supply Voltage Range
9.6V DC ... 30V DC
power consumption
≤ 2W (30V DC)
signal: digital
voltage input signal
0V DC ... 30V DC
current input signal
2 mA ... 15 mA
measurement
Input current range
0 A AC ... 100 A AC
-100 A DC ... 100 A DC
Measurement range
0 A AC/DC ... 50 A AC/DC
the setting range of the minimum input current
0 A AC/DC ... 9.4 A AC/DC
0 A AC/DC ... 18.8 A AC/DC
maximum input current
0 A AC/DC ... 62.5 A AC/DC (DIN/EN 61010-1)
0 A AC/DC ... 125 A AC/DC (DIN/EN 61010-1)
-125 A DC ... 125 A DC (DIN/EN 61010-1)
Overload
2 x IN(continuous), depending on the tie-in conductor