Phoenix MINI MCR-2-RPSS-I-I-feed isolator 2902014,3-end feed isolator, using plug-in connection technology. HART transparent, input signal 0(4)...20 mA, output signal 0(4)...20 mA. The device can be used in isolator and feeder isolator operations. Screw connection technology

Use Restrictions
EMC Description EMC: Class A products, see the manufacturer's declaration in the download area

Product Type Feeder Isolator
product series MINI Analog Pro
Channels 1
Model isolation amplifier
insulation characteristics: GB Standard
Overvoltage Category II
pollution level 2

electrical isolation 3 End Isolation
galvanic isolation between input and output is
cut-off frequency (3dB) > 1.75 kHz
protection circuit transient protection
Signal Transmission Behavior In = Out
step response (10-90%) < 200 & micro;s (typical)
maximum temperature coefficient 0.0075 %/K
temperature coefficient, typical 0.0075 %/K
Maximum transmission error 0.05 % (final value in repeater power supply operation)
0.1 % (final value in isolator operation)
Electrical isolation input/output/power supply
Rated insulation voltage 300Vrms
Test Voltage 3 kV AC (50 Hz, 60 s)
insulation reinforced insulation conforming to IEC/EN 61010-1
Power
Rated supply voltage 24V DC
Supply Voltage Range 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Typical current consumption 25 mA (24VDC, isolator operation)
50 mA (24VDC, feeder isolator operation)
55 mA (12VDC, isolator operation)
110 mA (12VDC, feeder isolator operation)
power consumption ≤ 1400 mW (IOUT= 20 mA,9.6V DC,600 Ω load)

signals: current
Input Description sensor circuit
Input Number 1
current input signal 0 mA ... 20 mA (Isolator operation)
4 mA ... 20 mA (feeder isolator and isolator operation)
input current (+0.7V for testing diodes)
Transmitter supply voltage > 19.5V

signals: current
outputs 1
No-load voltage < 20V
current output signal 0 mA ... 20 mA (Isolator operation)
4 mA ... 20 mA (feeder isolator and isolator operation)
Maximum current output signal 24 mA
load/output load current output ≤ 600 Ω (20 mA)
fluctuation < 20 mVSS(600 Ω)

Connection Mode screw connection
stripping length 10mm
thread M3
Rigid conductor cross section 0.2 mm² ... 1.5 mm² (with cold press head)
0.14 mm² ... 2.5 mm² (without cold head)
Flexible Wire Cross Section 0.14 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 12 (flexible)
Tightening torque 0.5 Nm ... 0.6 Nm

Explosion-proof installation (EPL) Gc
Div. 2

Data Communication (Bypass)
HART function is
cut-off frequency (3dB)  1.75 kHz

Status Display Green LED (supply voltage)
2902040

Phoenix MINI MCR-2-RPSS-I-I-Feed Isolator 2902014