Phoenix MCR-SL-S- 16-SP- 24-Current monitoring 2864464,MCR contactor for sinusoidal AC 0 ... 16A AC/1 Wechsler

Use Restrictions
EMC Description EMC: Class A products, see the manufacturer's declaration in the download area

Product Type Current transmitter
insulation characteristics
Overvoltage Category III
pollution level 2

Rated insulation voltage 300V AC (ground)
total error ≤ 1.4 % (temperature range)
Measurement Level III
test voltage, input/output 3.5 kV (50 Hz,1 min)
test voltage, input/power supply 3.5 kV (50 Hz,1 min)
protection circuit surge protection; 33V suppressor diode
step response (10-90%) 40 ms
maximum temperature coefficient < 0.02 %/K
power supply
Supply Voltage Range 20V DC ... 30V DC
Maximum current consumption < 30 mA

measurement:
Frequency measurement range 45Hz ... 60Hz
measurement
Input current range 0 A AC ... 16 A AC (Permissible continuous overload: 120%)
Overload 2xIN (sustained)
Rated frequency fN 50Hz
60Hz
Frequency measurement range 45Hz ... 65Hz
Curve Type Sine

switching: relay
Contact Type 1 changeover contact
Contact Material AgSnO, hard gold plating
maximum switching voltage 30V AC
36V DC
250V AC (when the gold plating layer is damaged)
limit continuous current 50 mA (gold-plated, 30V AC/36V DC)
2 A (250V AC if the gold plating is damaged)
response delay Typical 0.1 s ... 10 s (adjustable via potentiometer)

Connection Mode screw connection
stripping length 8mm
thread M3
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Connectable Guide Cross Section AWG 24 ... 14
Connection Mode perforated connection

Product Size
width 22.5mm
height 99mm
depth 114.5mm
Round wire
diameter 4.2mm
2814728

Phoenix MCR-SL-S- 16-SP- 24-Current monitoring 2864464

Product Center

PRODUCT CENTER