Phoenix MINI MCR-2-FM-RC-PT-monitoring module 2904508, the fault monitoring module adopts plug-in connection technology, which is used to evaluate and send reports on group errors of the FM system, and can also be used to monitor the power supply voltage. Fault information is reported through normally closed contacts. Plug-in connection technology, standard configuration
Product Type
Evaluation Unit
product series
MINI Analog Pro
configuration
DIP switch
insulation characteristics: GB Standard
Overvoltage Category
II
pollution level
2
Function
configuration
DIP switch
Rated insulation voltage
50V AC/DC (active)
electrical isolation
Foundation isolation according to EN 61010
test voltage (input/output)
1.5 kV AC (50 Hz, 60 s)
maximum temperature coefficient
< 0.01 %/K
electrical isolation
electrical isolation
input, power supply and output to switch output
power supply
Supply Voltage Range
9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Maximum current consumption
< 16 mA (24V DC)
power consumption
< 410 mW (24V DC)
signals: voltage
Input Description
Voltage inputs for redundant monitoring
Input Number
1
voltage input signal
9.9V DC ... 30V DC
switching: relay
maximum switching voltage
30V DC
maximum switching current
50 mA
signals: voltage
outputs
1
voltage output signal
9.6V DC ... 29.7V DC
Maximum current output signal
3.2 A
Connection Mode
in-line connection
stripping length
10mm
Rigid conductor cross section
0.2 mm² ... 2.5 mm² (with cold press head)
0.14 mm² ... 2.5 mm² (without cold head)
Flexible Wire Cross Section
0.14 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 12 (flexible)
Explosion-proof installation (EPL)
Gc
Div. 2
Status Display
Green LED (supply voltage)
yellow LED (switch output)
error indication
Red LED
width
6.2mm
height
109.81mm
depth
119.2mm
color
gray (RAL 7042)
Shell Material
PBT
railway vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection of railway vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
railway vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
environmental conditions
protection level
IP20 (not UL certified)
ambient temperature (operation)
-40°C ... 70°C
ambient temperature (storage/transport)
-40°C ... 85°C
elevation
≤ 2000 m
Allowable humidity (operating)
5%... 95% (non-condensing)
2902040