Phoenix MINI MCR-2-FM-RC-monitoring module 2904504, the fault monitoring module adopts plug-in connection technology, which is used to evaluate and send reports on group errors of the FM system, and can also be used to monitor the power supply voltage. Fault information is reported through normally closed contacts. Screw connection technology, standard configuration

Product Type Evaluation Unit
Product Series MINI Analog Pro
configuration DIP switch
insulation characteristics: GB Standard
Overvoltage Category II
pollution level 2

Function
configuration DIP switch

maximum temperature coefficient < 0.01 %/K
electrical isolation input/output EN 61010
Standards/Regulations EN 61010
Rated insulation voltage 50V AC/DC (active)
Test Voltage 1.5 kV AC (50 Hz, 60 s)
insulation Foundation Isolation
power supply
Supply Voltage Range 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Maximum current consumption < 16 mA (24V DC)
power consumption < 410 mW (24V DC)

signals: voltage
Input Description voltage input for redundant monitoring
Number of inputs 1
voltage input signal 9.9V DC ... 30V DC

switching: relay
maximum switching voltage 30V DC
maximum switching current 50 mA DC
signals: voltage
outputs 1
voltage output signal 9.6V DC ... 29.7V DC
Maximum current output signal 3.2 A

Connection Mode screw connection
stripping length 10mm
thread M3
Rigid conductor cross section 0.2 mm² ... 1.5 mm² (with cold press head)
0.14 mm² ... 2.5 mm² (without cold head)
Flexible Wire Cross Section 0.14 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 12 (flexible)
Tightening torque 0.5 Nm ... 0.6 Nm

Explosion-proof installation (EPL) Gc
Div. 2

Status Display Green LED (supply voltage)
yellow LED (switch output)
error indication Red LED

width 6.2mm
height 109.81mm
depth 119.2mm

color gray (RAL 7042)
Shell Material PBT
railway vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection of railway vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
railway vehicles (DIN EN 45545-2) R24 HL 1 - HL 2

environmental conditions
protection level IP20 (not UL certified)
ambient temperature (operation) -40°C ... 70°C
ambient temperature (storage/transport) -40°C ... 85°C
elevation ≤ 2000 m
Allowable humidity (operating) 5%... 95% (non-condensing)