Phoenix MACX MCR-EX-SL-2NAM-RO-SP-Isolation Amplifier 2924087,Ex I NAMUR Isolation Amplifier, Dual Channel. Proximity switches and switches for the Ex area. The signal is transmitted to the safety area through the relay output (normally open contact). Line fault detection (LFD),3-terminal isolation, SIL 2.

Product Type isolation amplifier
product series MACX Analog
Application Number IN
Channels 2
Model Ex I Isolation Amplifier with SIL Functional Safety
configuration DIP switch

Function
configuration DIP switch

electrical isolation 3 End Isolation
galvanic isolation between input and output is
rated conditions < 1W
electrical isolation input/output IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 375VPP
Overvoltage Category III
pollution level 2
galvanically isolated input/power supply, DIN rail connector IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 375VPP
Overvoltage Category II
pollution level 2
Electrically isolated input/power supply, DIN rail connector IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Overvoltage Category II
pollution level 2
insulation security isolation
Electrically isolated output 1/output 2/input, power supply, DIN rail connector IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Overvoltage Category III
pollution level 2
insulation security isolation
Electrically isolated output 1/output 2/input/power supply, DIN rail connector
Test Voltage 2.5 kV AC (50 Hz, 60 s)
Overvoltage Category III
pollution level 2
power supply
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption 35 mA (24V DC)
power consumption < 1W
power consumption < 1W

signal: NAMUR
Input Description Inoriginal Safety
Input Number 2
valid input source NAMUR proximity switch sensor (IEC/EN 60947-5-6)
Floating switch contact
Switch contacts with resistor circuit
input signal NAMUR
switch threshold "0" signal current < 1.2 mA (disabled)
switch threshold "1" signal, current > 2.1 mA (ON)
short-circuit current 8 mA
switching hysteresis < 0.2 mA
Line Fault Detection < 0.05 mA ... 0.35 mA (line break)
< 100 Ω ... 360 Ω (short circuit)
activated/deactivated via DIP switch
No-load voltage 8V DC