Phoenix MINI MCR-SL-U-UI-NC-isolation amplifier 2865007,MCR 3-terminal isolation amplifier, input/output configurable, used for electrical isolation and conversion of analog signals up to 30V, screw wiring, standard configuration
Product Type
isolation amplifier
product series
MINI Analog
Channels
1
configuration
DIP switch
insulation characteristics
Overvoltage Category
II
pollution level
2
electrical isolation
Foundation isolation according to EN 61010
galvanic isolation between input and output
is
cut-off frequency (3dB)
about 100Hz
protection circuit
transient protection
step response (10-90%)
about 3.5 ms
maximum temperature coefficient
< 0.01 %/K
temperature coefficient, typical
< 0.002 %/K
Maximum transmission error
< 0.1 % (of terminal value)
< 0.4 % (without mediation)
Electrical isolation input/output/power supply
Rated insulation voltage
50V AC/DC
Test Voltage
1.5 kV AC (50 Hz, 60 s)
power supply
Rated supply voltage
24V DC
Supply Voltage Range
19.2V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Maximum current consumption
< 19 mA (24VDC under load)
power consumption
< 450 mW
signals: voltage
Input Number
1
configurable/programmable
Yes, not configured
voltage input signal
0V ... 24V
0V ... 30V
Maximum voltage input signal
50V DC
input voltage
approx. 125 kΩ (0 ... 24V)
approx. 155 kΩ (0V ... 30V)
signal: current/voltage
outputs
1
configurable/programmable
Yes, not configured
voltage output signal
0V ... 10V
0V ... 5V
1V ... 5V
2V ... 10V
Maximum voltage output signal
≤ 12.5V
No-load voltage
≤ 12.5V
current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Maximum current output signal
28 mA
short-circuit current
≤ 22 mA
load/output load voltage output
> 10 kΩ
load/output load current output
< 500 Ω (when 20 mA)
fluctuation
< 20 mVSS(at 500 Ω)
< 20 mVSS(at 10 kΩ)
2864422
넳넲
Phoenix MINI MCR-SL-U-UI-NC-Isolation Amplifier 2865007