Phoenix MACX MCR-EX-SL-RPSSI-2I-SP-feed isolator 2924236,Ex I-measurement transmitter feed isolator and input isolation amplifier can transmit power supply from potentially explosive areas or active 0 mA/4 mA ... 20 mA current isolation signals to Two loads in the safe area. Number of Channels: 1, HART Transparent, Standard Configuration, 3-End Isolation, Safety Integrity Level (SIL, IEC 61508): 2, Performance Level (ISO 13849): d / KAT 2, Systematic Capability: 3, In-line Connection

Product Type Feeder Isolator
Product Series MACX Analog
Channels 1
Model Ex I Isolation Amplifier with SIL and PL Functional Safety

electrical isolation 3 End Isolation
galvanic isolation between input and output is
signal transmission behavior In = Out
step response (10-90%) 1.3 ms (for jumpers 4 mA ... 20 mA, typical)
maximum temperature coefficient < 0.01 %/K
Maximum transmission error < 0.1 % (final value 20 mA)
Typical transmission error < 0.05 % (final value 20 mA)
electrical isolation
Overvoltage Category II
pollution level 2
Electrically isolated input/output/power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Test Voltage 2.5 kV AC (50 Hz, 60 s)
insulation security isolation
electrical isolation input/output IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated input/power supply IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated output 1/output 2
Test Voltage 1.5 kV AC (50 Hz, 60 s)
Power
Name Feeder Isolator Operation
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 75 mA (24V DC / 20 mA)
power consumption < 1.45W (24V DC / 20 mA)
power consumption ≤ 1.8W
Power
Name Feeder Isolator Operation
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 46 mA (24V DC / 20 mA)
power consumption < 1.2W (24V DC / 20 mA)

signal: feeder isolator operation
Input Description Feeder Isolator Operation
Input Number 1
current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16V (20 mA)
> 15.1V (23 mA)
Polarization and Surge Protection is
undervoltage/overvoltage signal range 0 mA ... 24 mA (extended transmission range for diagnostics)
signal: feeder isolator operation
Input Description Feeder Isolator Operation
current input signal 0 mA ... 20 mA
4 mA ... 20 mA
voltage drop < 3.9V (input isolation amplifier operation)
undervoltage/overvoltage signal range 0 mA ... 24 mA (extended transmission range for diagnostics)
2865340