Phoenix MINI MCR-2-TC-UI-thermocouple measurement transmitter 2902055, a configurable temperature transmitter with plug-in connection technology, used to connect thermocouples. Configuration via DIP switch or software. Screw connection technology, standard configuration

Product Type temperature measurement transmitter
Product Series MINI Analog Pro
Model isolation amplifier
configuration DIP switch
Software
Application
insulation characteristics
Overvoltage Category II
pollution level 2

electrical isolation 3 End Isolation
Typical Cold Point Error 2 K (2 K +(0.2 K * ΔT))
protection circuit transient protection
step response (0-99%) 300 ms
570 ms
maximum temperature coefficient ≤ 0.01 %/K
transmission fault thermocouple signal 0.1% * 600 K/set measuring range; 0.1% > 600 K(C, E, J, K, N, T, L, U, M Gost, L Gost)
0.2 % * 600 K/set measuring range; 0.2 % > 600 K(B, R, S, A1, A2, A3)
0.2 % * 600 K/set measuring range; 0.2 % > 600 K(E, J, K, N, T, L, U, M Gost, L Gost);Highspeed Mode
0.4% * 600 K/set measuring range; 0.4% > 600 K(B, R, S, A1, A2, A3);Highspeed Mode
Electrical isolation input/output/power supply
Rated insulation voltage 300Vrms
Test Voltage 3 kV AC (50 Hz, 60 s)
insulation reinforced insulation conforming to IEC/EN 61010-1
power supply
Supply Voltage Range 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
Typical current consumption 32.7 mA (24V DC)
66.8 mA (12V DC)
power consumption ≤ 850 mW (IOUT= 20 mA,9.6V DC,600 Ω load)

signal
Input Number 1
measurement
Input Number 1
configurable/programmable is
Input Voltage Range - 500 mV ... 500 mV (can be set via software)
Available Sensor Types (TC) B, C, E, J, K, N, R, S, T, L, U, A- 1, A- 2, A- 3, M, L
Temperature measurement range -250°C ... 2500°C (range depends on the sensor type and can be set freely via software or incrementally from -150°C to 1350°C via DIP switch)
Temperature measurement range ≥ 50 K
Voltage Range 3 mV