Phoenix MINI MCR-2-TC-UI-PT-thermocouple measurement transmitter 2905249, a configurable temperature transmitter with plug-in connection technology, used to connect thermocouples. Configuration via DIP switch or software. Plug-in connection technology, standard configuration

Product Type temperature measurement transmitter
Product Series MINI Analog Pro
Model isolation amplifier
configuration DIP switch
Software
Application
insulation characteristics
Overvoltage Category II
pollution level 2

Function
configuration DIP switch
Software
Application

electrical isolation 3 End Isolation
Typical Cold Point Error 2 K (2 K +(0.2 K * ΔT))
protection circuit transient protection
step response (0-99%) 300 ms
570 ms
maximum temperature coefficient ≤ 0.01 %/K
transmission fault thermocouple signal 0.1% * 600 K/set measuring range; 0.1% > 600 K(C, E, J, K, N, T, L, U, M Gost, L Gost)
0.2 % * 600 K/set measuring range; 0.2 % > 600 K(B, R, S, A1, A2, A3)
0.2 % * 600 K/set measuring range; 0.2 % > 600 K(E, J, K, N, T, L, U, M Gost, L Gost);Highspeed Mode
0.4% * 600 K/set measuring range; 0.4% > 600 K(B, R, S, A1, A2, A3);Highspeed Mode
Electrical isolation input/output/power supply
Rated insulation voltage 300Vrms
Test Voltage 3 kV AC (50 Hz, 60 s)
insulation reinforced insulation conforming to IEC/EN 61010-1
Power
Supply Voltage Range 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be clamped to a 35mm DIN rail conforming to the EN60715 standard))
Typical current consumption 32.7 mA (24V DC)
66.8 mA (12V DC)
power consumption ≤ 850 mW (IOUT= 20 mA,9.6V DC,600 Ω load)

signal
Input Number 1
measurement
Input Number 1
configurable/programmable is
Input Voltage Range - 500 mV ... 500 mV (can be set via software)
Available Sensor Types (TC) B, C, E, J, K, N, R, S, T, L, U, A- 1, A- 2, A- 3, M, L
2902040

Phoenix MINI MCR-2-TC-UI-PT-Thermocouple Measurement Transmitter 2905249

Product Center