Phoenix ECM-UC-10A-UI-REL-current transmitter 1698164, a current transmitter used to measure alternating current, direct current and distortion current. Configuration via web server via USB-C interface (24V DC is not required). For current measurement range: 0 A ... 0.1 A to 0 A ... 12.5 A. Relay output, standard configuration, in-line connection
Product Type
Current transmitter
insulation characteristics
insulation
safety isolation conforming to IEC/EN 61010-1
Overvoltage Category
III (300 V)
pollution level
2
Electrical characteristics
step response (10-90%)
200 ms (AC/DC)
20 ms (DC)
maximum temperature coefficient
< 0.02 %/K
Maximum transmission error
0.5 % (under rated state, within rated range)
Rated insulation voltage
300V AC (ground)
electrical isolation IEC 61010-2-030
Standards/Regulations
IEC 61010-2-030
Measurement Type
III (300 V)
electrically isolated input/output
Test Voltage
4 kV AC (50 Hz, 60 s)
Electrically isolated input/power supply
Test Voltage
4 kV AC (50 Hz, 60 s)
galvanically isolated output/power
Test Voltage
2 kV AC (50 Hz, 60 s)
Power
Rated supply voltage range
12V DC ... 24V DC -20 % ... +25%
Supply Voltage Range
9.6V DC ... 30V DC
power consumption
≤ 2.3W (30V DC)
input data
signal: digital
voltage input signal
0V DC ... 30V DC
current input signal
2 mA ... 15 mA
measurement
Input current range
0 A AC ... 10 A AC
-10 A DC ... 10 A DC
Measurement range
0 A AC/DC ... 0.1 A AC/DC
0 A AC/DC ... 1 A AC/DC
0 A AC/DC ... 5 A AC/DC
the setting range of the minimum input current
0 A AC/DC ... 100 mA AC/DC
maximum input current
0 A AC/DC ... 12.5 A AC/DC (DIN/EN 61010-1)
0 A AC/DC ... 10 A AC/DC (UL 61010-1)
-12.5 A DC ... 12.5 A DC (DIN/EN 61010-1)
-10 A DC ... 10 A DC (UL 61010-1)
Overload
2 x IN
surge strength
10 x IN
Frequency measurement range
0Hz
10Hz ... 100Hz
10Hz ... 200Hz
10Hz ... 500Hz
10Hz ... 1000Hz
Curve Type
AC, DC, or distorted current
output data
switching: relay
Contact Type
1 changeover contact
Contact Material
AgNi
Minimum Switching Voltage
12V (10 mA)
maximum switching voltage
250V AC
48V DC
limit continuous current
6 A AC (250V AC, 50/60 Hz)
1 A DC (48V DC)
signal: current/voltage
voltage output signal
0V ... 10V
0V ... 5V
1V ... 5V
2V ... 10V
-10V ... 10V
-5V ... 5V
10V ... -10V
5V ... -5V
10V ... 0V
5V ... 0V
current output signal
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
load/output load voltage output
> 10 kΩ
load/output load current output
< 500 Ω